RELEASE NOTES
PowerAlert Device Manager 15.5.4 (Build 1045)
31-JAN-2019

Copyright (c) 2019 by Tripp Lite
All Rights Reserved

REQUIREMENTS
* PowerAlert Mass Updater Utility version 1.1.0 (Build 17134) or higher can be used to upgrade
  prior versions of 15.x to 15.5.4.

DEFECT FIXES
* Corrected erroneous General Fault alarm on 4000 protocol
* Corrected problem causing lock up under certain circumstances after an extended period of runtime
* Corrected Battery Capacity reporting at startup on PS8813 (4201 protocol)
* Corrected Shutdown controls failing to turn output back on after turning UPS off on 3005 protocol

ENHANCEMENTS
* Added support for USB->RS232 adapter to support RS232 Console Servers

KNOWN ISSUES
* Shutdown Device is written twice to the event log
* tlpEnvOutputContactCurrentState is not writable
* Device ID is not editable on 5009 and 5022 protocols
* An apostrophe character used when naming an action is rejected and causes consoles to log out
* Power On Delay always displays as zero for 5017 protocol
* Low and High Transfer Bounds are reported incorrectly for 5017 protocol
* Shutdown Device schedule does not work for 3005 protocol
* Low Transfer Voltage and High Transfer Voltage are not reported in the wrong magnitude via SNMP for 5017 protocol
* Output Line Count is not displayed for certain devices
* Number of Phases is not displayed for certain devices
* Incorrectly displaying Enable Online Mode for certain devices
* upsSecondsOnBattery not supported
* Saving an auto probe via Menu interface will display an error when no IP address is specified on a disabled probe
* Clearing the default auto probes do not reset all changed fields to original values
* Modifying delay for the default email action may disassociate that action from events
* SNMPv2c not supported for Set OID actions
* Serial numbers are not editable using SNMP for devices that do not support serial numbers
* The web interface automatically logs out after a period of inactivity when the timeout period is disabled
* A space character is rejected when used for naming a device
* A space character used when entering a date is rejected and causes consoles to log out
* Incorrectly displaying Device Shutdown action when not supported by a device
* Incorrectly displaying Output Off event when not supported by a device
* Entering a session or inactivity timeout greater than 32767 locks Administrator out of web GUI sessions
* Configuring ACL for non-SNMP users is rejected
* sysContact is not configurable
* BMS serial number is not reported via SNMP for 3018 protocol
* System allows user to send turn on and off device multiple times in a row
* System does not obtain an IP address from DHCP if network is not available during bootup
* Fan Always On and Remote Setpoint do not return to original value after dehumidifying event
* Fan Always On can be set after Remote Setpoint is disabled
* Reboot device will not operate properly if restart time is less than shutdown time
* "Save and Reboot" after changing a subnet mask sometimes does not save the change
  -- Use save without reboot, then reboot the card instead
* Changing a subnet mask to a value not in conformance with one's network will prevent all remote access to the system
* tlpCoolingQuietMode is listed in MIB as read-write, but should be read-only
* tlpCoolingHotGasBypass is listed in MIB as read-write, but should be read-only
* Hovering the mouse over role, keyword and importance in Device Settings display incorrect values
* Lowest temperature setting (63 degrees) does not save for 9002 protocol
* Battery Age on 4006 protocol does not update and remains zero when Last Battery Replace Date exceeds 36 months
* Device Mode on 4006 protocol does not show Standby after placing the unit in Standby mode
* Reset Battery Transition Count should be listed as a Reset Control
* Water Full/Not Full messages appear during power cycles on 9002 protocol
* Operating Mode displays Not Connected when the LX card is disconnected on a 9002 Protocol
  -- Reboot unit to correct
* Load importance selector allows for choose values out of range
  -- Valid range: 1-100
* Incorrect Nominal Output Voltage selections are presented on a 4201 protocol
* Nominal Output Voltage cannot be configured on a 4201 protocol
* Enable Online Mode should be listed as an Enable Control
* Auto Fan Speed does not automatically update on the GUI panel using IE
  -- Updates are correct using Chrome and Firefox
* Device ID reverts back to zero(0) regardless of value saved on SM8896 (3021 protocol)
* Battery Minutes Remaining does not display a value when on battery on PS6794 (4100 protocol)
* Battery Age Above Threshold alarm does not clear after changing replacement dates on PS6794 (4100 protocol)
* General Fault alarm does not trigger on PS6794 (4100 protocol)
* Output Off alarm does not trigger on PS6794 (4100 protocol)
* Output Calculated Power (KW) reports inaccurate value on PD88BF (5013 protocol)
* tlpPduOutletGroupIndex reports incorrect index value
* Device ID is not editable on 5009 protocol
* SNMP reports incorrect number of bypass lines supported by the 3-phases UPS (4201 protocol)
* Communications Lost category cannot be modified via Menu interface
* Unable to enable or disable bypass mode via SNMP
* SNMP reports battery voltage incorrectly (4201 protocol)
* Battery Warning value does not change when device enters Battery Low condition (4201 protocol)
* Output Power is reported twice (4000 protocol)
* Self Test Status does not update after executing self test (4201 protocol)
* Fan status not supported by UUT (4000 protocol)
* Output Source reports normal when main load is off (3005 protocol)
* Output Current Above/Below Threshold alarms are not cleared once the output current returns to normal (5017 protocol)
  -- Set hysteresis for theshold values to at least 0.5A
* Nominal Input Frequency does not report a value (4000 protocol)
* Phase voltage type is not reported through SNMP
* Setting a contact's email log format to CSV reverts to XML after rebooting device
* Wrong number of breakers are reported (5017 protocol)

END RELEASE NOTES